Sign In | Join Free | My ecer.jp
ecer.jp
Products
Search by Category
Home > Transformers >

Current Voltage Transformers 1mA CT PT Testing Equipment

Categories CT PT Testing Equipment
Brand Name: RISING
Model Number: RSFA-103
Certification: ISO CE
Place of Origin: China
MOQ: 1
Payment Terms: L/C, D/A, D/P, T/T, Western Union, MoneyGram
Supply Ability: 500 SET PER Month
Delivery Time: 5-8 days
Packaging Details: Wooden package for export
  • Haven't found right suppliers
  • Our buyer assistants can help you find the most suitable, 100% reliable suppliers from China.
  • And this service is free of charge.
  • we have buyer assistants who speak English, French, Spanish......and we are ready to help you anytime!
Submit Buying Request
  • Product Details
  • Company Profile

Current Voltage Transformers 1mA CT PT Testing Equipment

RSFA-103 Multi-function CT PT Analyzer


Product Introduction

The products put into the market after a lot of market researches, strict field tests and the authoritative department identification by our R & D team. Instrument adopts high performance data processing and microcomputer control architecture, advanced manufacturing process, to ensure the product performance stable and reliable, fully functional, high degree of automation, high test efficiency, is a professional protection box of high voltage insulation used to test current voltage transformers specialized detection equipment.


Products Features

1.Safe and convenient to operate: Full micro-computerized devices, built-in imported high-performance CPU, with high reliability, according the prompt of the interface to set test values, you need not touch the tested equipment, the equipment automatically finish the test, the test personnel far from high voltage circuit ,to ensure their personal safety.

2.Full-featured: CT volt-ampere characteristic test, inflection point calculation and error curve, CT ratio polarity test, contrast calculation, secondary side circuit inspection, PT volt-ampere characteristic test, PT ratio polarity test. Automatically records show that all kinds of test results, and can save the print test records, real-time instrument comes with the clock function, greatly convenient for the user to document the test report.

3.High output capacity: the maximum output voltage for volt-ampere characteristic tests up to 1000V, external booster (optional) can be maximum increased to 2500V, variable ratio test and a flow-through test maximum current 600A,the output capacity of equipment is 5KVA, can do the volt-ampere characteristic test of 500kV,1A current transformers.

4.Large-screen 320 × 240 dot matrix character graphical interface, directly display volt-ampere characteristic curve after the test, graphics are clear, aesthetic, easy to analyze, equipped with micro-printer, can print the curves and test results at any time.

5.Built-in Flash memory device can store large amounts of test data, which will not be lost after power off. When the filed tests finished, people can check and print the tests results indoors.

6.U-disk dump: support U disk to dump test data, through PC to read, easy to operate.

7.PC with powerful software, beautiful outlook, easy to operate, can save and print the test results, convenient to manage the test data.

8.Apparatus can achieve AC220V and AC380V adaptive power supply. When the AC power input terminals connected to AC220V voltage, AC voltage output is 0 ~ 600 V, when the input terminals to AC380V voltage, AC voltage output is 0 ~ 1000 V. Users can choose according to actual needs.


Technical Parameters

Power supplyAC380VAC220V
CT volt-ampere characteristic teststand-alone0~1000V,0~20A0~600V,0~20A
external booster(optional)0~2500V,0~3A0~2000V,0~3A
Resolution0.1V,1mA
Accuracy≤0.5%
5% or 10% error curveAccuracy≤1.0%
CT ratio testRange5~25000A/5A(5000A/1A)
Accuracy≤1.0%
PT volt-ampere characteristic teststand-alone0~1000V,0~20A0~600V,0~20A
external booster(optional)0~2500V,0~3A0~2000V,0~3A
Resolution0.1V,1mA
Accuracy≤0.5%
PT ratio polarity testRange1~10000
Accuracy≤1.0%
Primary current injectingCurrent Range0~600A
Current injecting time5 min
Power supply voltageAC220V or AC380V 50HZ
Working environment temperature-10℃ ~ +50℃
host volume420×330×320mm3
host weight39kg
external booster (optional)volume310×310×330mm3
external booster (optional)weight25kg

Cheap Current Voltage Transformers 1mA CT PT Testing Equipment for sale
Send your message to this supplier
 
*From:
*To: Wuhan Rising Electric Co., Ltd.
*Subject:
*Message:
Characters Remaining: (0/3000)
 
Inquiry Cart 0