Sign In | Join Free | My ecer.jp |
|
Categories | Server Rack Mount Air Conditioner |
---|---|
Brand Name: | Coolnet |
Model Number: | CI05,09 |
Certification: | CE/ISO9001 |
Place of Origin: | China |
MOQ: | 1 |
Price: | $500.00-5000.00/set |
Payment Terms: | T/T |
Supply Ability: | 1000-5000/set/month |
Delivery Time: | 4W |
Packaging Details: | WOODED |
Cooling Capacity: | 3.5KW-9KW |
Color: | Black/Grey white/other custom colors |
Mounting: | Rack mountnting |
Power: | 1N-220V-50Hz,110v/50hz/60hz |
Air Flow: | 750-1100M3/H |
Application: | cabinet/ intelligent project and medium & small sized enterprise |
Height: | 5U,9U |
Type: | Split |
Voltage: | 220V, 380V |
Company Info. |
Hefei Coolnet power Co., ltd |
Verified Supplier |
View Contact Details |
Product List |
Server Rack Cooling Rack-Mount Air Conditioning Cooling Capacity 7,000 BTU / 2.0 KW
Product Introduction In-Rack is the most precise cooling available, as the rack and the air conditioner operate in a closed relationship with one another. Cold air has no choice but to pass through the servers; hot air has no choice but to pass through the heat exchanger. In-Rack cooling provides a computing environment-a microclimate-that is thermally neutral to the rest of the room. Feature & Benefits | ![]() |
Characteristic & Advantages
![]() | High-level Configuration ▪ High-efficiency inverter compressor, ultra-precise PID control, more precise temperature control. ▪The well-known EC centrifugal fan can adjust the air volume output ratio in real time as needed. ▪Equipped with electronic expansion valve, smoothly adjust the throttle opening, realize precise adjustment of the unit. ▪Outdoor motor chopper speed regulation, which can realize 25-100% wide voltage speed regulation control. ▪R410A environmentally friendly refrigerant design. Safe & Reliable ▪Very wide grid adaptability, can meet ±20% voltage range, adapt to various harsh grid environments. ▪Multi-drainage and anti-back flow design to prevent cabinet flooding. ▪Intelligent self-detection of refrigerant capacity and intelligent early warning to ensure the safe operation of the refrigeration system. High Intelligent ▪High-efficiency inverter compressor, ultra-precise PID control technology. ▪Unique vibration compensation algorithm to realize broadband operation of the unit. ▪Safe and reliable anti-condensation algorithm to ensure the safe operation of the server. Easy Installation & Maintenance ▪Standard modular design to fit into standard server racks. ▪The design of plug-in terminals on the fan side and the whole machine makes the whole machine easy to maintain and fast to install; it occupies a small area and has 100% full frontal maintenance. ▪Refrigeration piping is connected with quick couplings. Various Options ▪Strong drainage of condensate ▪Wet film humidifier ▪Electric heater |
Applications
| ![]() |
Indoor Unit Parameters
Model-CJA | 0003 | 0005 | 0007 | 0012 | |||
Phase/Function | 1.5P,Single Phase | 2P,Single Phase | 3P,Single Phase | 5P,Single Phase | |||
Parameters | |||||||
Cooling capacity kW | 3.5 | 5 | 7.5 | 12.5 | |||
Sensible cooling capacity k | W 3.5 | 5 | 7.5 | 12.5 | |||
Air volume m³/h | 800 | 1150 | 1600 | 2300 | |||
Sensible heat ratio % | 100 | 100 | 100 | 100 | |||
Heating kW (Option) | 1 | 1 | 2 | 3 | |||
Maximum operating current A | 15 | 15 | 25 | 34 | |||
Power Cord Cable Specifications | mm 3×2.5 | 3×2.5 | 3×4 | 3×6 | |||
Indoor/outdoor unit shut-off valve | |||||||
Refrigerant gas pipe φ mm | 12.7 | 12.7 | 12.7 | 15.88 | |||
Refrigerant liquid pipe φ mm | 9.52 | 9.52 | 9.52 | 9.52 | |||
Indoor unit structural parameters | |||||||
Dimension:W×D×H mm | 442×714×175 (4U) 442×714×218 (5U) | 442×714×218 (5U) | 442×714×351 (8U) | 442×714×440 (10U) | |||
Outdoor Unit | |||||||
Type-CJT | 3005 | 3005 | 3008 | 3013 | |||
Quantity | 1 | 1 | 1 | 1 |
Outdoor Unit Parameters
Type- CJT | 3005 | 3005 | 3008 | 3013 | |||
Power supply | 220Vac/1Ph/50Hz | ||||||
Installation | Vertical | ||||||
Speed mode | Stepless speed regulation | ||||||
Noise dBA | 54 | 55 | 56 | 58 | |||
Rated current A | 6 | 6 | 10 | 15 | |||
Power Cord Cable Specifications | mm 4×1.5 | 4×1.5 | 4×2.5 | 4×4 | |||
Communication cable specificati mm (with shielding function) | on 3×1 | 3×1 | 3×1 | 3×1 | |||
Structural parameters of outdoor unit | |||||||
Dimension:W×D×H mm | 840×285×610 | 840×285×610 | 880×360×800 | 930×390×1270 |
① The power cord of the outdoor unit must be connected from the indoor unit;
Certificates
Factory Details
Packing & Delivery