Replaceable Dwyer Differential Air Pressure Switch

Categories Hvac Pressure Switch
Brand Name: Keramcontrols
Model Number: QAD
Certification: CE,RoHS
Place of Origin: China
MOQ: 10
Payment Terms: L/C, T/T
Delivery Time: 7days
Packaging Details: Carton
Model: QAD
Contact Arrangement: SPDT
Media: Air,non-combustible and non-aggressive gasses
Max Operating Pressure: 10kPa
Mounting Position: Diaphragm in any vertical plane
Degree of protection: IP54(with cover)
Operating Temperature: -40℃to 85℃
  • Haven't found right suppliers
  • Our buyer assistants can help you find the most suitable, 100% reliable suppliers from China.
  • And this service is free of charge.
  • we have buyer assistants who speak English, French, Spanish......and we are ready to help you anytime!
Submit Buying Request
  • Product Details
  • Company Profile

Replaceable Dwyer Differential Air Pressure Switch

Replaceable Dwyer Differential Air Pressure Switch


Description


QAD differential pressure switch is used for fan status and dirty filter applications. A knob with pressure values on it allows the setpoint to be adjusted visually in the field. The plastic duct probe tubes, flexible silicon tubing and the mounting screws are included with all models.


Technical Specifications


ModelQAD
MediaAir,non-combustible and non-aggressive gasses
Max Operating Pressure10kPa
Mounting PositionDiaphragm in any vertical plane
Degree of protectionIP54(with cover)
Operating Temperature-40℃to 85℃
Contact ArrangementSPDT
Electrical RatingResistance: Initial: < 50 milliohms;
Current1.5A resistive(0.4A inductive) 250V
Electric Connection6.3x0.8 blade 46244 or screw terminals
MaterialHousing:ABS
Duct connectors: ABS
Membrane: Silicone
Cable sleeve:PVC
Weight0.15kg(0.35kg with flexible pipe)
Connectionφ6.0mm for tube connection
ApprovalUL,CE,RoHS

Dimensions(mm)



Installation Connections


QAD series air pressure controls is factory-calibrated for vertical position. If installed horizontally, this will affect the switching point as following:

• with cover facing upwards, switching point is 15Pa higher than scale;

• with cover facing downwards, switching point is 15Pa lower than scale.


Note: Do not install upside down with trip pressures of less than 50pa!


Electric Wiring


Product Range


ModelPressure RangeDifferentialTolerance
QAD-120~200Pa10Pa±15%
QAD-230~300Pa10Pa±15%
QAD-340~400Pa20Pa±15%
QAD-450~500Pa20Pa±15%
QAD-5200~1000Pa100Pa±15%
QAD-6500~2500Pa150Pa±15%
QAD-71000~5000Pa250Pa±15%
  • The performances stated in this sheet can be modified without any prior notice due to design improvements