Sign In | Join Free | My ecer.jp
ecer.jp
Products
Search by Category
Home > Uninterrupted Power Supply (UPS) >

3 Phase Low Frequency Online UPS Pure Sine Wave Power Supply for Telecom

Categories Low Frequency Online UPS
Brand Name: SOROTEC
Model Number: GP9335C 10-800KVA
Certification: CE,ROHS,RSO9000
Place of Origin: China
MOQ: 2PCS
Price: 10000USD
Payment Terms: L/C, T/T, Western Union
Supply Ability: 3000PCS Per Month
Delivery Time: Within 15-30days after receiving your 30% TT deposit
Packaging Details: Standard Exported Cartons and Pallets
Product: Low Frequency Online UPS
Phase: Three phase
Output Power Factor: 0.9
Capacity: 10-800KVA
Output Voltage: 380/400/415VAC
Input Voltage: 380/400/415VAC 3-phase 4-wire
Frequency: 50/60HZ
DC Voltage: 360/384/432/480VAC
Protection Level: IP20
Weight: 980 -7390KG
Dimension(w*d*h): 900*855*1900MM
System Efficiency: 94% (Full loads)
Application: Data center,industry,servers
  • Haven't found right suppliers
  • Our buyer assistants can help you find the most suitable, 100% reliable suppliers from China.
  • And this service is free of charge.
  • we have buyer assistants who speak English, French, Spanish......and we are ready to help you anytime!
Submit Buying Request
  • Product Details
  • Company Profile

3 Phase Low Frequency Online UPS Pure Sine Wave Power Supply for Telecom

3 Phase Low Frequency Pure Sine Wave Online UPS Power Supply for Telecom


Key Features:
1.Use advanced 6th generation DSP and full digital control technologies to realize higher system stability.


2.Output power factor is 0.9, carrying capacity than conventional UPS with 10% above, as users reduce investment cost.


3.Advanced distributed active parallel technology can realize parallel operation of 6PCS UPS units without the need of centralized bypass cabinet.


4.6-inch extra large LCD that can display 12 language (Chinese ,English,Russian,Spanish,French and so on).


5.Extra wide input voltage and frequency range make it adapt to severe power grid environment


6.Intelligent battery management maintains battery automatically to prolong the battery life.


7.Standard input/output filter improves the system EMC performance.


8.Extra strong capability to withstand output overload and short circuit, ensuring the system stability and system safety under extreme conditions.


9.Layered independently-sealed ventilation channel and re-dundant fan, circuit boards with protective paints and a dust filter embedded make it highly efficient to dissipate heat and protect the product effectively under severe environment.


GP9335C Series Technical Specification:

ModelGP9335C
Rectifier Type6p12p6p12p6p12p6p12p6p12p
Rated Nominal120KVA/108KW160KVA/144KVA200KVA/180KW300KVA/270KW400KVA/360KW
Rated input voltage380/400/415VAC 3-phase 4-wire
Rated frequency50/60HZ
Input parameters
Input voltage range±25%
Input frequency range45Hz~65Hz
Input soft start function0-100% 5-300settable
Input power factor>0.98(If harmonic filter is added)
Input harmonic current (THDi)‹4.5%(If harmonic filter is added)
Bypass
Bypass voltage range-20%~+15%
Bypass frequency range50/60HZ±10%
Output parameters
Inverter output voltage380/400/415VAC 3-phase 4-wire
Voltage stability±1%(Steady status),±3%(Transient status)
Frequency50/60Hz
Mains power synchronization window±5%
Actually measured frequency accuracy (internal clock)50/60Hz±0.01Hz
Output power factor0.9(Output 90kW per 100kVA)
Transient response time<5ms
Inverter overload capabilityAt 0.9 power factor, 110% for 1 hour, 125% for 10 minutes and 150% for 60s
3ph 1.5ln for 5seconds,1ph 2.9ln for 5seconds
Short circuit current from inverter
Maximum Bypass capability1000% for 100ms
With 100% balanced load<1°
Phase shift
characteristicWith 100% imbalance load<1°
100% linear load<1%
Total harmonic
Distortion(THDv)100% non-linear load<3%
System efficiency (full load)Up to 94% (inverter efficiency is up to 98%)
Rectifier output parameters
Charger output voltage stability1%
DC ripple voltage≤1%
Operating environment
Operating temperature range0~40°C
Storage temperature-25~70°C(Without battery)
Relative humidity0~95% No condensation
Noise (1m)58-68dB
Protection levelIP20
StandardSafety: IEC60950-1 IEC62040-1-1 UL1778 EMC IEC62040-2 CLASS C2 EN50091-2 CLASS A Design andTest IEC62040-3

Applications:
Mainly used in large IDC rooms, bank/securities settlement center, communication network management center, semiconductor product lines and large automation production and its control system. According to the special needs of users was improved, and used in large sports venues, conference room, theater and highway and railway tunnels metal halide lamp lighting system.