Sign In | Join Free | My ecer.jp |
|
Categories | Uninterrupted Power Supply |
---|---|
Place of Origin: | China |
Brand Name: | SOROTEC |
Certification: | CE,ROHS,ISO9000 |
MOQ: | USD10000 |
Packaging Details: | Standard Exported Cartons and Pallets |
Delivery Time: | Within 15-30days after receiving your 30% TT deposit |
Payment Terms: | 30% TT in advance, the balance before shipping |
Supply Ability: | 10000PCS/Month for Inverter and line Interactive UPS; Advance 3000PCS/Month for Online UPS |
Model Number: | HP9116B 6-10KVA |
Rated Voltage: | 200/208VAC |
Frequency: | 50/60 Hz |
Voltage Range: | 176~279VAC(±3VAC) |
Frequency Range: | 50HZ:(46~54HZ); 60HZ:(56HZ~64HZ) |
Power Factor: | 0.98 |
Voltage Regulation: | 200/208X (1±2%)VAC |
Frequency Regulation: | 50/60 Hz±0.05Hz |
Power factor: | 0.7/0.8(Optional) Standard 0.7 |
RS232 interface 0.7 1ph in / out 110V UPS 10KVA / 8000W with bypass repair switch
Key Features:
1.Widely used to computer equipments, telecommunication systems and
Industrial automatic control equipments.
2.Truly online design, different from offline, it can adjust the
input voltage, filtering, when the AC break off, the UPS will
provide an uninterruptible power source from the backup batteries.
3.Large blue back light LCD for detailed Real-time UPS status display.
4.Advanced online pure sine wave power supply system, with bypass
repair switch, It can
provide a reliable, high quality AC power source to the precision
equipments, can be used widely in different fields.
5.UPS will change to bypass mode when overloading or inverter
fault, when overloading remove, UPS will turn to inverter mode
automatically.
6.N+N Parallel Redundancy and Capacity expansion for 6-20K(up to
three units)
Applications:
Servers, Data-center, critical network devices, Sensitive
electronic equipment, Telecom…
Model | HP9116B 6-10KVA | ||||
6KT | 6KT-XL | 10KT | 10KT-XL | ||
Rated Power | 6KVA/4800W | 10KVA/8000W | |||
Rated Voltage | 200/208VAC | ||||
Frequency | 50/60 Hz | ||||
Input | |||||
Voltage Range | 176~279VAC(±3VAC) | ||||
Frequency Range | 50HZ:(46~54HZ); 60HZ:(56HZ~64HZ) | ||||
Power Factor | 0.98 | ||||
Output | |||||
Voltage Regulation | 200/208X (1±2%)VAC | ||||
Frequency Regulation | 50/60 Hz±0.05Hz | ||||
Power factor | 0.7/0.8(Optional) Standard 0.7 | ||||
Voltage distortion | Linear load<3% Non-linear load<6% | ||||
Overload Capability | 110%~150% for 30s | ||||
Current Crest Ratio | 3;1 | ||||
Transfer time | 0ms(AC mode→ Battery mode) | ||||
Battery | |||||
DC Voltage | 240VDC | ||||
Recharge Time | 7hrs to 90% of capacity after | ||||
Recharge Current | 2A | 4.2A | 2A | 4.2A | |
Display | |||||
LCD | Display input/output Voltage, | ||||
Communication | |||||
Interface | Smart RS232, SNMP card | ||||
Environment | |||||
Operation Temperature | 0~40℃ | ||||
Humidity | 0~95% non-condensing | ||||
Storage Temperature | -25℃~55℃ | ||||
Sea level elevation | <1500m | ||||
Noise Level(1m) | <55dB | ||||
Physical Characteristic | |||||
Wright(KG) | N.W. | 81 | 35.5 | 84 | 36 |
G.W. | 89 | 39.5 | 91 | 42 | |
Dimension(D x W x H)mm | 570 X260 X717 |
![]() |